Technical Spec

The PowPak™ Relay Module is a radio frequency (RF) device capable of controlling up to 5 A of general-purpose load based on input from Pico® controls and Radio Powr Savr™ occupancy and daylight sensors. An optional, low-voltage dry contact closure output is available to communicate occupancy status to 3rd-party systems such as HVAC controllers. Communication with RF input devices, such as Pico® controls and Radio Powr Savr™ sensors, is accomplished using Lutron Clear Connect™ RF Technology.

Features and Benefits

  • Capable of switching 5 A of general-purpose loads
  • Optional low-voltage dry contact closure output provides integration to building management systems, HVAC, VAV, etc.
  • Various operating voltages available—refer to model number chart below for details on voltage requirements
  • Receives wireless inputs from up to nine Pico® controls, six Radio Powr Savr™ occupancy/vacancy sensors, and one Radio Powr Savr™ daylight sensor
  • Utilizes Lutron Clear Connect™ RF Technology – refer to model number chart below for frequency band data
  • Mounts to a junction box through a standard half-inch (NPT trade size) knockout
  • Complies with requirements for use in a compartment handling environmental air (plenum) per NEC® 2011 300.22(C)(3)
Model # RMJ-5RCCO1-DV-B
Operating voltage: 120/277 V~ 50 / 60 Hz
System Communication
  • Operates using Clear Connect™ RF Technology for reliable wireless communication; refer to model number chart on page 1 for frequency band details
  • RF range is 30 ft (10 m)
Environment
  • Ambient operating temperature: 32 °F to 131 °F (0 °C to 55 °C)
  • 0% to 90% humidity, non-condensing
  • For indoor use only
Load Types
  • Maximum load: 5 A general purpose. No minimum load requirements.
  • Load types include (but are not limited to):
    – Incandescent
    – MLV
    – ELV
    – Resistive
    – Inductive
    – Magnetic fluorescent
    – Electronic fluorescent
Key Design Features
  • LED status indicator shows current load status and provides programming feedback
  • Power failure memory: If power is interrupted, connected loads will return to the previous level prior to interruption