Robertson AV Guides
Equipment Rack Basics: Sizes, Ventilation, and Power
By Robertson AV ·
A processor that overheats every afternoon, a breaker that trips when the amplifiers come up, a switcher that won’t fit because nobody checked depth: these rack problems are far cheaper to solve on paper than on site. This guide covers the three decisions behind every good AV rack setup: how big the rack needs to be, how heat gets out, and how power gets in.
Rack sizes: units, width and depth
What a rack unit is
Rack-mount AV and IT gear follows the EIA-310 standard for 19-inch racks. One rack unit (1U) is 1.75 inches (44.45 mm) of vertical mounting space. Micropolis’s rack mounting FAQ explains that the “19-inch” name comes from the equipment front panel, which is 19 inches (482.6 mm) wide including the mounting ears, with 17.75 inches of clear opening between the rails.
The rail holes repeat in groups of three. Cisco’s rack-mount instructions for an EIA-310-D rack give the vertical spacing as 0.50, 0.625 and 0.625 inches, repeating, with each U starting and stopping in the middle of the 0.50-inch gap. They also give the horizontal hole spacing as 18.312 inches (465.1 mm).

Choosing rack height
Rack height is quoted in U, so the math is simple: a 24U rack gives 24 x 1.75 = 42 inches of mounting space, not counting the frame, base or top. Size it in this order:
- List every rack-mount device and its height in U from the spec sheet.
- Add shelves for non-rack-mount gear, such as small media players or network switches without ears.
- Add space for the rack PDU, any UPS, cable management and the blank or vent panels your cooling plan calls for.
- Add room to grow. Middle Atlantic’s thermal management paper points out that racks should be designed for future expansion, because adding gear later often compromises a thermal design that worked on day one.
Depth, rails and form factor
Depth trips up more projects than height. Check the deepest device, then add room behind it for connectors, power cords and the bend radius of HDMI, HDBaseT and network cables. Check rail spacing too: slide rails for heavier equipment are often designed for a specific front-to-back post distance. The Cisco guide above, for example, lists a supported post spacing range for its slide rails, and other manufacturers publish their own.
Form factor follows the room: wall-mount racks for a few devices, floor-standing racks for equipment closets, and credenza cabinets for conference rooms without a closet. Credenzas are small enclosed spaces, so ventilation matters even more.
Ventilation: getting heat out of the rack
Start with the heat load
Nearly every watt an electronic device draws ends up as heat. Middle Atlantic’s white paper Controlling the Temperature Inside Equipment Racks uses these working figures:
- One watt of draw equals 3.413 BTU/hr of heat.
- At 117 volts, each amp of current draw produces about 400 BTU/hr.
- 85°F is the maximum recommended constant operating temperature inside the rack for most equipment, and for digital equipment the room should be no hotter than 75°F.
The same paper warns against using nameplate ratings alone. Nameplates show maximum draw for safety approval, not typical heat. In its example of a videoconferencing rack, the equipment nameplates added up to 16.9 amps while the measured draw was 2.54 amps. Use measured or published typical power where you can, and get waste-heat figures for amplifiers from their manufacturer.
Passive convection: no fans
According to the Middle Atlantic paper, a rack in a normal room can shed roughly 300 to 500 watts of heat through natural convection. That only works with a clear “chimney”: vents at the bottom and top of the rack, none in the middle, and nothing blocking the air path inside. Under passive cooling, hotter equipment placed lower in the rack creates more natural airflow.
The most common mistake the paper calls out is adding vent panels between every device. With front-intake equipment, those vents let hot air short-circuit back into the intakes. If your gear has no vents on its top or bottom, it’s fine to stack it directly.
Forced air: when to add fans
When the load is beyond what convection can handle, fans take over. The paper’s rules of thumb:
- A top-of-rack fan’s CFM should be at least the sum of the equipment fans’ CFM. It notes most front-intake equipment fans are between 25 and 50 CFM each.
- A fan’s CFM rating is a free-air maximum. Once it’s mounted in an enclosure, real airflow drops.
- Use a solid rear door, and avoid vent panels in the upper six spaces of the rack, so the fan pulls air through the equipment instead of straight from the nearest opening.
- Where conditioned space is limited, separate amplifier racks from digital audio and video racks. Amplifiers tolerate more heat than processors and network gear.

Fill every empty space
Open rack spaces let hot exhaust loop back to the front. APC’s White Paper 44, Improving Rack Cooling Performance Using Airflow Management Blanking Panels, measured a 22°F (12°C) drop in inlet temperature for the hottest server in its test rack, the one just above an open space, once a blanking panel covered the gap. Install blanks in every unused space and use brush or pass-through panels where cables cross.
Power: PDUs, circuits and power strips
Plan around the 80% rule
In North America, cord-connected rack power distribution units (PDUs) are rated below the circuit that feeds them. Vertiv’s rack PDU FAQ explains that, because the NEC sizes branch circuits for 125% of the continuous load, a cord-connected rack PDU’s nameplate current is 80% of its branch circuit rating. A 16A PDU needs a 20A breaker. The FAQ adds two checks that matter in AV racks:
- Don’t load any receptacle beyond its own rating. A NEMA 5-15R outlet shouldn’t carry more than 15A, whatever the PDU nameplate says.
- For PDUs with internal breakers, Vertiv recommends loading each breaker to no more than 80% of its rating to avoid nuisance trips.
Total the rack’s expected draw, check it against the PDU and circuit, and have the facility’s electrician confirm the circuits before install.

Power strips are not rack power
Consumer power strips are listed by UL as relocatable power taps (RPTs). UL’s guidance, reprinted in its Question Corner for code authorities, says RPTs are meant to plug directly into a permanently installed receptacle. They aren’t meant to be daisy-chained to other power taps or extension cords, permanently secured to structures, or used as a substitute for fixed wiring. Use a PDU built for rack mounting, follow its listing and instructions, and plug it straight into the circuit planned for it.
Heat follows power
Power and cooling are the same budget. Every watt on the PDU becomes 3.413 BTU/hr that the rack and room have to remove, so finish the power ledger first and use it to size ventilation. If the rack also needs battery backup for network gear or control processors, budget the UPS’s rack space and weight early. Schools comparing UPS and rack funding can see our guide to what E-Rate covers for racks and UPS.
AV rack setup checklist
- List every device with its height in U, depth, typical power draw and airflow direction.
- Size height with room for the PDU, panels and growth. Size depth for the deepest device plus cables.
- Convert the power total to BTU/hr and decide on passive or forced-air cooling.
- Lay out the elevation: heavy gear low, blanks in every empty space, vents only where the cooling plan puts them.
- Match PDUs and circuits to the load using the 80% rule, with no daisy-chained power strips.
- Plan signal runs out of the rack. Our HDBaseT extender guide covers long HDMI runs from a rack to remote displays, and our digital signage media player guide covers players that often end up on a rack shelf.
- Choose the displays on the other end with the same duty-cycle thinking. See our commercial display vs consumer TV checklist.
FAQ
How tall is 1U?
1.75 inches (44.45 mm). A 2U device takes 3.5 inches, and a 12U rack provides 21 inches of mounting space.
Does every AV rack need a fan?
No. Middle Atlantic puts passive convection at roughly 300 to 500 watts of heat in a normal room, with vents at the top and bottom. Beyond that, or in a warm closet, plan for forced air.
Can I plug a power strip into a rack PDU?
UL’s guidance says relocatable power taps should plug directly into a permanently installed receptacle and not be daisy-chained, so plug equipment into the PDU and add PDU capacity if you run out of outlets.
Should amplifiers go at the top or bottom of the rack?
It depends on the cooling method. With passive convection, the Middle Atlantic paper places hotter gear lower. In hot environments with fans, it shows amplifiers at the top, and warns that heavy gear up high makes unanchored racks easy to tip.
Can RobertsonAV quote a complete rack package?
Yes. Send your device list, room or closet details and power information through a quote request, or browse our racks. Shipping is free on all RobertsonAV orders within the United States, including oversized and heavy items. Some items need a scheduled delivery, and the carrier will contact you to arrange a delivery window. If you need liftgate or inside delivery, mention it on your quote request. Our guides to requesting an AV quote that gets approved and buying AV equipment with a purchase order explain the rest of the process.